May Eca cables still be used?
‹ Terug naar overzicht- May Eca cables still be used?
Answer: The Building Decree 2012 has been amended as of 1 June 2020. For new installations, the use of Eca cables in contact with indoor or outdoor air is no longer permitted.
The Environment Buildings Decree, which replaces the Building Decree from 1 January 2024, has the same requirements.
Eca cables are only allowed where they do not come into contact with indoor or outdoor air, e.g. cast in a concrete wall.
- › May Eca cables still be used?
- What is the CPR?
- What is the fire class or Euro class?
- Are separate GST and BST connectors also covered by CPR?
- What is the difference between smoke classes s1, s1a and s1b?
- Do connecting conduits to appliances have to meet the fire class requirements set in CPR or Environment Buildings Decree (BBL)?
- Are separate GST and BST connectors also covered by CPR?
- Are GST18 cables in furniture also covered by CPR and NEN1010?
- What is the fire classification of old GST18 cables from before CPR legislation?