Answer: If a connector joint (combination of a male and a female connector) is part of the electrical
installation, it is important to know how much load this connection can be subjected to.NEN1010 is the standard with which an installation in the Netherlands must comply.
This states that connectors may be used in a fixed installation to connect through cabling and appliances. (559.5.3 and 526) These so-called installation connector joints shall comply with product standard NEN-EN-IEC 61535. This includes:
The current cycle test
An installation connector joint according to NEN-EN-IEC 61535 shall preferably have a rated current according to one of the following values:
Rated current (A)
Test conductor mm²
Test current (A)
10
1,5
12,5
13
1,5
16,25
16
1,5
20,0
20
2,5
25,0
25
4,0
31,0
32
6,0
40,0
The connector joint must then be tested according to the rules prescribed in NEN-EN-IEC 61535, including a duration test of 384 cycles of 1 hour. The test current is thereby 25% higher than the specified rated current, and testing is performed with the core cross-section specified in the table.
The voltage drop across the connector joint is directly related to the current, contact resistance and temperature of the connection, and these must remain within set limits during and after the test. If the connector joint meets the test requirements, it may be used safely.
The test must be carried out by an accredited testing and certification institute. At Wieland, tests and certifications for Europe are often carried out by the VDE.
Example:
If we fit an installation connector joint in a domestic system in a group with 16A protection, 1.5mm² or 2.5mm² wiring is chosen. The connector must obviously be specified for this wire thickness. And the rated current load capacity of the connector joint should be at least 16A.
Each connector for a pluggable connection has a technical specification.
This specification includes details on the rated current that may permanently flow across the contacts. Some examples from the Wieland connector range
Connector
Rated current(A)
Rated voltage (V)
Diameter connection (mm²)
GST15i3
16
250
0,5 – 2,5
GST18i3
20
250
0,75 – 2,5
GST18i5
20
250 / 400
0,75 – 2,5
RST16i3
16
250 / 400
0,25 – 2,5
RST20i3
20
250 of 400
0,5 – 2,5
RST20i5
20
250 / 400
0,75 - 4
RST25i3
25
250
0,75 - 6
RST50i4/5
50
250 / 400
4 - 16
How much current is allowed through a permanent pluggable connection in an installation?
- › How much current is allowed through a permanent pluggable connection in an installation?
- Is it important to lock pluggable electrical connections?
- Are there any applications where locking is not required?
- Can you fit pluggable electrical installations to cable trays?
- Can a pluggable electrical connection be made in a cable duct?
- Is it mandatory to lock pluggable electrical connections?
- Was it also mandatory to lock pluggable electrical connections in the past? Did other standards apply then?