Is an LED Limiter only for new installations?

A LED Limiter also be retrofitted in old installations. If it is a pluggable installation it is actually very easy

  1. Is an LED Limiter only for new installations?
  2. Has the application of circuit breakers affected the installation?
    "

    The cable length in the installation affects safe shut-down. As the response value increases, the cable length becomes shorter. (Section 41 NEN1010)

    "
  3. What can you do to combat inrush current?
    "

    Regulating the inrush current prevents an inrush surge. You can do that with an LED Limiter (current-limiting resistor)

    "
  4. Is fluorescent lighting also subject to inrush current?
    "

    Yes, due to the coils, a surge of about 5x Inom. occurs.

    "
  5. What inrush current is an LED fixture subject to?
    "

    The inrush current surge is usually described in the technical documentation. In some cases, this can be as high as 100 x Inom.

    "
  6. Can I replace fluorescent lighting 1-to-1 for LED lighting?
    "

    One light will not be a problem. But if there are many, there will be a huge inrush current. You can avoid this by fitting an LED Limiter.

    "
  7. How many LED bulbs can go on 1 group?
    "

    Without measures, only a few fixtures can go on 1 group. If the fixtures are switched on at the same time, you can calculate how many there should be. Often the supplier specifies how many can be switched on at once. 

    "
  8. Can a motion sensor switch LED lights?
    "

    Here’s a closer look at what the maximum current of the switch should be. This is between 4 and 10 Amps. If larger current surges are regularly switched, the contacts will burn.

    "
  9. Is it possible to put an LED Limiter in any circuit?
    "

    As long as the technical details are followed, it can be done.

    "
  10. Is LED lighting mandatory?
    "

    Yes, the government has specified for buildings that, in terms of sustainability, LED lighting should be used.

    "
  11. Where can I fit the LED Limiter?
    "

    Wherever multiple LED fixtures need to be switched simultaneously.

    "
  12. Is the LED Limiter pluggable?
    "

    The LED Limiter features Wieland GST18i3® connectors with black coding.

    "
  13. How high is the inrush current of an LED lamp?
    "

    The inrush current surge is usually described in the technical documentation. In some cases, this can be as high as 100 x Inom.

    "
  14. How many LED fixtures can be connected to the LED Limiter?
    "

    The LED Limiter can be loaded up to 8A. So the total rated current of all fixtures connected to it may be 8A combined.

    "
  15. How heavily can the LED Limiter be loaded?
    "

    The LED Limiter can be loaded up to 8A. So the total rated current of all fixtures connected to it may be 8A combined.

    "
  16. Can you connect 2 LED Limiters to a group?
    "

    Yes, on a 16A group one may place 2 LED Limiters which can both be loaded to 8A.

    "
  17. Can you connect multiple LED Limiters to a group?
    "

    Yes, multiple LED Limiters may be connected to a group. As long as the maximum current of the group is not exceeded.

    "
  18. How high is the inrush current when using an LED Limiter?
    "

    The LED Limiter eliminates the inrush current surge of the LED fixtures connected to it. So there is no more inrush current surge (at power-on). The current remains at its nominal value.

    "
  19. What is the part number of the LED Limiter?
    "

    ICL8A200

    "
  20. What is inrush current?
    "

    Inrush current surge

    "
  21. What devices cause inrush current?
    "

    LED drivers, among others. All devices with capacitors or coils in the supply section.

    "
  22. What causes inrush current?
    "

    Capacitors are included in LED driver circuits. When the voltage is switched on, the resistance is close to 0 ohms for a short time. This means the current is almost infinite. After a few milliseconds, this effect disappears.

    "
  23. How does inrush current affect switches and relays?
    "

    The enormously high current surge can cause contacts to burn-in. After a longer time, a resistance develops across the contact which causes heat generation.

    "
  24. How does inrush current affect screw-type fuses?
    "

    A fuse is a slow protection device but will melt through at a certain value. The higher the surge the faster the fuse melts.

    "
  25. What impact does inrush current have on circuit breakers?
    "

    A circuit breaker will switch off at a certain current surge. The higher the surge the faster the breaker shuts down.

    "
  26. What maximum inrush is permissible for switches?
    "

    Many switching elements are capable of switching 10A. This is stated in the technical description.

    "
  27. What maximum inrush is permissible for fuses?
    "

    Depending on the type of fuse, a different surge is permissible. For detailed information, see the technical information of the fuse.

    "
  28. What maximum inrush is permiss+C164ible for circuit breakers?
    "

    Depending on the type of circuit breaker, it will trip at a surge of B-5, C-10 or D-20 times that circuit breaker’s rated current.

    "
  29. What circuit breakers can be used?
    "

    Normally, B-breakers are used. In exceptional cases C-breakers. In industrial applications, D-breakers are used. Please note that replacing a B circuit breaker with a C circuit breaker halves the maximum permissible length of the installation, as the minimum short-circuit current (10xIn) doubles.

    "