What can you do to combat inrush current?

Regulating the inrush current prevents an inrush surge. You can do that with an LED Limiter (current-limiting resistor)

Contact us
    1. Has the application of circuit breakers affected the installation?
      "

      The cable length in the installation affects safe shut-down. As the response value increases, the cable length becomes shorter. (Section 41 NEN1010)

      "
    2. What can you do to combat inrush current?
      "

      Regulating the inrush current prevents an inrush surge. You can do that with an LED Limiter (current-limiting resistor)

      "
    3. Is fluorescent lighting also subject to inrush current?
      "

      Yes, due to the coils, a surge of about 5x Inom. occurs.

      "
    4. What inrush current is an LED fixture subject to?
      "

      The inrush current surge is usually described in the technical documentation. In some cases, this can be as high as 100 x Inom.

      "
    5. Can I replace fluorescent lighting 1-to-1 for LED lighting?
      "

      One light will not be a problem. But if there are many, there will be a huge inrush current. You can avoid this by fitting an LED Limiter.

      "
    6. How many LED bulbs can go on 1 group?
      "

      Without measures, only a few fixtures can go on 1 group. If the fixtures are switched on at the same time, you can calculate how many there should be. Often the supplier specifies how many can be switched on at once. 

      "
    7. Can a motion sensor switch LED lights?
      "

      Here’s a closer look at what the maximum current of the switch should be. This is between 4 and 10 Amps. If larger current surges are regularly switched, the contacts will burn.

      "
    8. Is it possible to put an LED Limiter in any circuit?
      "

      As long as the technical details are followed, it can be done.

      "
    9. Is an LED Limiter only for new installations?
      "

      A LED Limiter also be retrofitted in old installations. If it is a pluggable installation it is actually very easy

      "
    10. Is LED lighting mandatory?
      "

      Yes, the government has specified for buildings that, in terms of sustainability, LED lighting should be used.

      "
    11. Where can I fit the LED Limiter?
      "

      Wherever multiple LED fixtures need to be switched simultaneously.

      "
    12. Is the LED Limiter pluggable?
      "

      The LED Limiter features Wieland GST18i3® connectors with black coding.

      "
    13. How high is the inrush current of an LED lamp?
      "

      The inrush current surge is usually described in the technical documentation. In some cases, this can be as high as 100 x Inom.

      "
    14. How many LED fixtures can be connected to the LED Limiter?
      "

      The LED Limiter can be loaded up to 8A. So the total rated current of all fixtures connected to it may be 8A combined.

      "
    15. How heavily can the LED Limiter be loaded?
      "

      The LED Limiter can be loaded up to 8A. So the total rated current of all fixtures connected to it may be 8A combined.

      "
    16. Can you connect 2 LED Limiters to a group?
      "

      Yes, on a 16A group one may place 2 LED Limiters which can both be loaded to 8A.

      "
    17. Can you connect multiple LED Limiters to a group?
      "

      Yes, multiple LED Limiters may be connected to a group. As long as the maximum current of the group is not exceeded.

      "
    18. How high is the inrush current when using an LED Limiter?
      "

      The LED Limiter eliminates the inrush current surge of the LED fixtures connected to it. So there is no more inrush current surge (at power-on). The current remains at its nominal value.

      "
    19. What is the part number of the LED Limiter?
      "

      ICL8A200

      "
    20. What is inrush current?
      "

      Inrush current surge

      "
    21. What devices cause inrush current?
      "

      LED drivers, among others. All devices with capacitors or coils in the supply section.

      "
    22. What causes inrush current?
      "

      Capacitors are included in LED driver circuits. When the voltage is switched on, the resistance is close to 0 ohms for a short time. This means the current is almost infinite. After a few milliseconds, this effect disappears.

      "
    23. How does inrush current affect switches and relays?
      "

      The enormously high current surge can cause contacts to burn-in. After a longer time, a resistance develops across the contact which causes heat generation.

      "
    24. How does inrush current affect screw-type fuses?
      "

      A fuse is a slow protection device but will melt through at a certain value. The higher the surge the faster the fuse melts.

      "
    25. What impact does inrush current have on circuit breakers?
      "

      A circuit breaker will switch off at a certain current surge. The higher the surge the faster the breaker shuts down.

      "
    26. What maximum inrush is permissible for switches?
      "

      Many switching elements are capable of switching 10A. This is stated in the technical description.

      "
    27. What maximum inrush is permissible for fuses?
      "

      Depending on the type of fuse, a different surge is permissible. For detailed information, see the technical information of the fuse.

      "
    28. What maximum inrush is permiss+C164ible for circuit breakers?
      "

      Depending on the type of circuit breaker, it will trip at a surge of B-5, C-10 or D-20 times that circuit breaker’s rated current.

      "
    29. What circuit breakers can be used?
      "

      Normally, B-breakers are used. In exceptional cases C-breakers. In industrial applications, D-breakers are used. Please note that replacing a B circuit breaker with a C circuit breaker halves the maximum permissible length of the installation, as the minimum short-circuit current (10xIn) doubles.

      "
    Our knowledge partners
    • naamloos-1641287912-1648131607.png
    • nen_logo_lid_van_normcommissie_klein2-1643711156-1648131689.jpg
    • logo-fedet-retine-klein-1641287912-1-1648130055.png
    • iso9001-16-1641287912-1648131141.png
    • soiec27001-1715778747.jpg
    • logo_2ba-1641287912-1648131309.png
    • picture-compano-120x100-1643653571-1648131395.png
    • isso-label-partner-rgb-1641287912-1-1648131490.png
    Receive our newsletter

    The world around is changing rapidly. But we will keep you up to date – for free!